type: "ABB"
nummer: "ABB-0100"
abb_id: "ABB-0100"
abb_nummer: "NE02"
naam: "OSI RM Laag 1 Koppeling Datacenters"
archimate_type: "Grouping"
laag: "Netwerk"
auteur: "R. Groenewoud"
status: "Niet vermeld"
gerelateerde_adrs: ["ADR-G01", "ADR-G56"]
archimate_element: "id-31380"
archimate_grouping: "id-31380"
archimate_technology_service: ["id-30641"]
archimate_view: "id-29930"
ontwerp_paragraaf: "5.2.1"
ontwerp_link: "../../input/markdown/NDS%20Overheidsbrede%20Soevereine%20Clouddienst%20Ontwerp%20v0.9.md#positionering-abb-osi-rm-laag1-koppeling-datacenters"
ontwerp_paragrafen: ["5.2.1"]
ontwerp_links: ["../../input/markdown/NDS%20Overheidsbrede%20Soevereine%20Clouddienst%20Ontwerp%20v0.9.md#positionering-abb-osi-rm-laag1-koppeling-datacenters"]
---

# ABB-0100: OSI RM Laag 1 Koppeling Datacenters

```mermaid
%%{init: {"flowchart": {"nodeSpacing": 20, "rankSpacing": 40, "padding": 12, "subGraphTitleMargin": {"top": 0, "bottom": 24}}}}%%
flowchart TB
    %% id-31379 -> id-31380 (Grouping)
    subgraph v_id_31379["ABB: OSI RM Laag 1 Koppeling Datacenters"]
        direction TB
        %% id-31381 -> id-30641 (TechnologyService)
        v_id_31381["OSI RM Laag 1 Koppeling Datacenters"]
    end
    %% id-31382 -> id-31383 (Grouping)
    subgraph v_id_31382["ABB: Cloud Availability Zone"]
        direction TB
        %% id-31384 -> id-31385 (Location)
        subgraph v_id_31384["Cloud Availability Zone"]
            direction TB
            %% id-31386 -> id-31387 (Grouping)
            subgraph v_id_31386["ABB: Datacenter Gebouw"]
                direction TB
                %% id-31388 -> id-31389 (Facility)
                subgraph v_id_31388["Datacenter Gebouw"]
                    direction TB
                    %% id-31390 -> id-31378 (Facility)
                    v_id_31390["Meet-Me-Room (MMR)"]
                end
            end
        end
    end
    %% id-31391 -> id-31383 (Grouping)
    subgraph v_id_31391["ABB: Cloud Availability Zone"]
        direction TB
        %% id-31392 -> id-31385 (Location)
        subgraph v_id_31392["Cloud Availability Zone"]
            direction TB
            %% id-31393 -> id-31387 (Grouping)
            subgraph v_id_31393["ABB: Datacenter Gebouw"]
                direction TB
                %% id-31394 -> id-31389 (Facility)
                subgraph v_id_31394["Datacenter Gebouw"]
                    direction TB
                    %% id-31395 -> id-31378 (Facility)
                    v_id_31395["Meet-Me-Room (MMR)"]
                end
            end
        end
    end
    %% id-31396 -> id-31383 (Grouping)
    subgraph v_id_31396["ABB: Cloud Availability Zone"]
        direction TB
        %% id-31397 -> id-31385 (Location)
        subgraph v_id_31397["Cloud Availability Zone"]
            direction TB
            %% id-31398 -> id-31387 (Grouping)
            subgraph v_id_31398["ABB: Datacenter Gebouw"]
                direction TB
                %% id-31399 -> id-31389 (Facility)
                subgraph v_id_31399["Datacenter Gebouw"]
                    direction TB
                    %% id-31400 -> id-31378 (Facility)
                    v_id_31400["Meet-Me-Room (MMR)"]
                end
            end
        end
    end
    v_id_31390 -->|Serving| v_id_31381
    v_id_31395 -->|Serving| v_id_31381
    v_id_31400 -->|Serving| v_id_31381
    style v_id_31381 fill:#d6f8b8,stroke:#000000,color:#111111
    style v_id_31379 fill:#ffffff,stroke:#585858,color:#111111,stroke-dasharray:4 3
    style v_id_31390 fill:#d6f8b8,stroke:#000000,color:#111111
    style v_id_31388 fill:#d6f8b8,stroke:#000000,color:#111111
    style v_id_31386 fill:#ffffff,stroke:#585858,color:#111111,stroke-dasharray:4 3
    style v_id_31384 fill:#efd1e4,stroke:#000000,color:#111111
    style v_id_31382 fill:#ffffff,stroke:#585858,color:#111111,stroke-dasharray:4 3
    style v_id_31395 fill:#d6f8b8,stroke:#000000,color:#111111
    style v_id_31394 fill:#d6f8b8,stroke:#000000,color:#111111
    style v_id_31393 fill:#ffffff,stroke:#585858,color:#111111,stroke-dasharray:4 3
    style v_id_31392 fill:#efd1e4,stroke:#000000,color:#111111
    style v_id_31391 fill:#ffffff,stroke:#585858,color:#111111,stroke-dasharray:4 3
    style v_id_31400 fill:#d6f8b8,stroke:#000000,color:#111111
    style v_id_31399 fill:#d6f8b8,stroke:#000000,color:#111111
    style v_id_31398 fill:#ffffff,stroke:#585858,color:#111111,stroke-dasharray:4 3
    style v_id_31397 fill:#efd1e4,stroke:#000000,color:#111111
    style v_id_31396 fill:#ffffff,stroke:#585858,color:#111111,stroke-dasharray:4 3
```

## Positionering ABB “OSI RM Laag1 Koppeling Datacenters”

![Figuur 5‑5 Positionering ABB OSI RM Laag1 Koppeling Datacenters](<../../input/markdown/media/media/image21.svg>)

De datacenters die samen een Cloud Region vormen, worden onderling gekoppeld door een OSI RM Laag-1 netwerk.

Samenvatting uitgangspunten, architectuurkeuzes en aandachtspunten:

- Maximum afstand tussen datacenters binnen Cloud Region bepaald door synchrone storage-replicatie.